Detailed content
Order-Code Interpretation
RET543: transformer terminal type
A: auxiliary voltage / digital input voltage group
M: Multi functionality level
243: hardware configuration
AAAB: display, software and language configuration identifiers
Technical Specifications
Platform: RET 54_ transformer terminal family
Analog Inputs: multiple CT and VT channels depending on hardware
Digital Inputs: 25 inputs for RET 543 base configuration
Digital Outputs: 18 outputs including HSPO, PO and SO types
Programming: IEC 61131-3 function block logic
Configuration Tool: CAP 505 / Relay Configuration Tool
Protection & Control Functions
Transformer differential and restricted earth fault
Overcurrent and earth fault protection
Thermal protection
Breaker failure protection
OLTC tap-changer control
Breaker and disconnector control
Self-supervision and internal diagnostics
Measurement Functions
Current and voltage calculation
Power, energy and frequency
Neutral current and zero-sequence voltage calculation
RTD temperature monitoring with optional extension cards
Communication Interfaces
RS-485 and optional communication modules
Protocols: Modbus, DNP 3.0, IEC 60870-5-103, SPA and other substation protocols depending on module
Functional Features
High-speed power outputs for trip commands
Internal temperature monitoring
Auxiliary voltage failure indication
Sequence-of-event and fault data recording
Flexible MIMIC and logic configuration
Application Scenarios
Two-winding and multi-winding transformer protection, substation automation, power plants, industrial substations and retrofit protection projects.
Installation Requirements
Panel-mounted installation with secure earthing.
Confirm CT/VT polarity and ratio before connection.
Match hardware number and functionality level with project design.
Download and verify configuration with approved setting file.
Usage Precautions
Verify trip-matrix and interlocking logic before energizing.
Do not mix hardware versions without compatibility check.
Test HSPO outputs under safe simulated conditions.
Maintain backup of parameter, logic and MIMIC configuration.














.jpg)