ABB REF541KM118AAAA
Product Name
REF 541 Feeder Protection and Control Terminal
Product Overview
Multifunctional medium-voltage protection terminal integrating protection, control, measurement, power-quality monitoring and substation communication in a single intelligent electronic device.
Detailed content
Technical Specifications
Series: Relion 500 / REF 54_ feeder terminal
Current Inputs: 1 A or 5 A configurable
Voltage Inputs: 100 / 110 / 120 V class
Rated Frequency: 50 / 60 Hz
Display: graphical LCD with local control keys
Front Protection: IP54
Rear Protection: IP20
Protection Functions
Phase and earth fault overcurrent
Directional overcurrent
Thermal overload
Overvoltage and undervoltage
Zero-sequence voltage protection
Breaker failure protection
Automatic reclosing
Measurement Functions
Current, voltage, frequency, power factor
Active and reactive power
Energy metering
Harmonics and power-quality disturbance recording
Communication Interfaces
RS-485, Ethernet and service ports
Protocols: IEC 60870-5-103, DNP 3.0, Modbus, IEC 61850 with gateway
Time synchronization through digital inputs or IRIG-B depending on configuration
Functional Features
Programmable logic and interlocking
Local and remote breaker control
Circuit-breaker condition and trip-circuit monitoring
Fault recording and sequence-of-event logging
Integrated PLC-like functionality
Application Scenarios
MV feeder protection, incoming and outgoing switchgear, cable protection, motor protection, capacitor bank protection and distribution automation.
Installation Requirements
Panel cut-out mounting in switchgear.
Confirm auxiliary voltage range before energizing.
Use proper CT/VT wiring with separate grounding.
Configure protection settings with PCM600 or compatible tool.
Usage Precautions
Verify current and voltage rating before commissioning.
Test trip logic and interlocking offline first.
Do not modify protection settings without authorized configuration backup.
Inspect terminal torque and insulation after installation.