ABB PL810P 3BDH000311R0101

Product Introduction‌

The PL810P is an ABB power link module used in ABB Advant OCS and FieldIT systems. It supplies bus power to a PROFIBUS PA segment and, together with an HS810, HS820 or HS840 head station, forms an LD 800P linking device. It does not perform complex programming tasks and acts as a fieldbus power supply, signal coupling and isolation unit that links the PROFIBUS DP side with the PROFIBUS PA side.

Detailed content

‌Technical Specifications‌

Product type: power link module

System family: Advant OCS and FieldIT

Matching head stations: HS810, HS820, HS840

Fieldbus protocols: PROFIBUS DP V1 and PROFIBUS PA

PA segment baud rate: 31.25 kbit per second

PA segment voltage: 24 V to 26 V

PA segment current: not more than 400 mA

Module supply voltage: 20 V to 35 V DC

Module supply current: approximately 400 mA to 790 mA

Supply ripple: not more than 10 percent

Terminating impedance: integrated 100 ohm

Isolation: functional isolation with a designed isolation voltage of 50 Veff

EMC requirement: compliant with NAMUR NE 21

Hazardous area suitability: usable in Zone 2

Explosion protection certificate: TUV 02 ATEX 1886 X

Explosion protection type: II 3 G EEx nA II T4

Applicable standards: EN 50170/2, IEC 61158-2, EN 50178

Dimensions: approximately 80 mm x 115 mm x 92 mm

Weight: approximately 0.34 kg

‌Performance Parameters‌

PA segment rate: 31.25 kbit per second

PA segment maximum current: 400 mA

Supply voltage range: 20 V to 35 V DC

PA segment voltage: 24 V to 26 V

Isolation voltage: 50 Veff

Terminating impedance: 100 ohm

Ripple requirement: not more than 10 percent

Operating area: Zone 2

Isolation boundaries: channel to PROFIBUS DP, PROFIBUS PA to supply, channel to supply

‌Functional Features‌

Direct bus power supply for the non-intrinsically safe PROFIBUS PA segment

Forms an LD 800P linking device together with an HS8x0 head station

Requires no programming, since the module itself needs no separate program configuration

Pluggable terminals for convenient field wiring and maintenance

Integrated terminating resistor that simplifies PROFIBUS PA segment termination

Functional isolation between power, DP side and PA side

Usable in Zone 2 areas

‌Material Composition‌

Housing: industrial flame-retardant plastic

PCB substrate: multi-layer printed circuit board

Power circuit: DC to DC conversion and bus supply circuit

Bus interface circuit: PROFIBUS DP and PA communication interface

Isolation components for power and signal separation

Pluggable terminals for power and bus wiring

Metal fixing parts for rail or cabinet mounting

‌Structure Characteristics‌

A modular housing that mounts in an ABB system rack or a matching installation position. The front section carries the power, DP connection and PA segment terminals. It works together with the head station through terminal connections, and provides an independent PA output for the non-intrinsically safe PROFIBUS PA segment. Status indication is provided through the module indicators for supply and communication state.

‌Application Scenarios‌

Chemical process control systems

Oil and gas field instrument power supply

Power industry fieldbus networks

Pharmaceutical process monitoring

Water treatment plant instrument segment power supply

Pulp and paper process control

DCS systems that require PROFIBUS PA segment power

Replacement parts for legacy ABB Advant OCS systems

‌Working Principle‌

The PL810P receives 20 V to 35 V DC system power and converts it through its internal power circuit to the voltage required by the PROFIBUS PA segment, then supplies field instruments over the PA bus. The head station handles protocol conversion and data exchange between PROFIBUS DP and PA, while the PL810P provides PA segment power, signal coupling and isolation. The module provides functional isolation between power, the DP side and the PA side to reduce interference and improve system reliability. The PA segment runs at 31.25 kbit per second and can connect multiple PA devices, with the actual number limited by bus current, power consumption and segment design.

‌Installation Requirements‌

Use only in combination with an HS810, HS820 or HS840 head station. Confirm that the system supply is 20 V to 35 V DC before installation. Distinguish the power terminals, DP terminals and PA terminals when wiring. PROFIBUS PA segment cabling must conform to the PROFIBUS PA wiring specification. Do not connect intrinsically safe field devices directly to the non-intrinsically safe PA segment. For installation in Zone 2, observe the electrical rules for explosion-protected areas. Keep the module away from heat sources and ensure adequate ventilation. Check terminating resistors and polarity after wiring is complete.