ABB PL810P 3BDH000311R0101
Product Introduction
The PL810P is an ABB power link module used in ABB Advant OCS and FieldIT systems. It supplies bus power to a PROFIBUS PA segment and, together with an HS810, HS820 or HS840 head station, forms an LD 800P linking device. It does not perform complex programming tasks and acts as a fieldbus power supply, signal coupling and isolation unit that links the PROFIBUS DP side with the PROFIBUS PA side.
Detailed content
Technical Specifications
Product type: power link module
System family: Advant OCS and FieldIT
Matching head stations: HS810, HS820, HS840
Fieldbus protocols: PROFIBUS DP V1 and PROFIBUS PA
PA segment baud rate: 31.25 kbit per second
PA segment voltage: 24 V to 26 V
PA segment current: not more than 400 mA
Module supply voltage: 20 V to 35 V DC
Module supply current: approximately 400 mA to 790 mA
Supply ripple: not more than 10 percent
Terminating impedance: integrated 100 ohm
Isolation: functional isolation with a designed isolation voltage of 50 Veff
EMC requirement: compliant with NAMUR NE 21
Hazardous area suitability: usable in Zone 2
Explosion protection certificate: TUV 02 ATEX 1886 X
Explosion protection type: II 3 G EEx nA II T4
Applicable standards: EN 50170/2, IEC 61158-2, EN 50178
Dimensions: approximately 80 mm x 115 mm x 92 mm
Weight: approximately 0.34 kg
Performance Parameters
PA segment rate: 31.25 kbit per second
PA segment maximum current: 400 mA
Supply voltage range: 20 V to 35 V DC
PA segment voltage: 24 V to 26 V
Isolation voltage: 50 Veff
Terminating impedance: 100 ohm
Ripple requirement: not more than 10 percent
Operating area: Zone 2
Isolation boundaries: channel to PROFIBUS DP, PROFIBUS PA to supply, channel to supply
Functional Features
Direct bus power supply for the non-intrinsically safe PROFIBUS PA segment
Forms an LD 800P linking device together with an HS8x0 head station
Requires no programming, since the module itself needs no separate program configuration
Pluggable terminals for convenient field wiring and maintenance
Integrated terminating resistor that simplifies PROFIBUS PA segment termination
Functional isolation between power, DP side and PA side
Usable in Zone 2 areas
Material Composition
Housing: industrial flame-retardant plastic
PCB substrate: multi-layer printed circuit board
Power circuit: DC to DC conversion and bus supply circuit
Bus interface circuit: PROFIBUS DP and PA communication interface
Isolation components for power and signal separation
Pluggable terminals for power and bus wiring
Metal fixing parts for rail or cabinet mounting
Structure Characteristics
A modular housing that mounts in an ABB system rack or a matching installation position. The front section carries the power, DP connection and PA segment terminals. It works together with the head station through terminal connections, and provides an independent PA output for the non-intrinsically safe PROFIBUS PA segment. Status indication is provided through the module indicators for supply and communication state.
Application Scenarios
Chemical process control systems
Oil and gas field instrument power supply
Power industry fieldbus networks
Pharmaceutical process monitoring
Water treatment plant instrument segment power supply
Pulp and paper process control
DCS systems that require PROFIBUS PA segment power
Replacement parts for legacy ABB Advant OCS systems
Working Principle
The PL810P receives 20 V to 35 V DC system power and converts it through its internal power circuit to the voltage required by the PROFIBUS PA segment, then supplies field instruments over the PA bus. The head station handles protocol conversion and data exchange between PROFIBUS DP and PA, while the PL810P provides PA segment power, signal coupling and isolation. The module provides functional isolation between power, the DP side and the PA side to reduce interference and improve system reliability. The PA segment runs at 31.25 kbit per second and can connect multiple PA devices, with the actual number limited by bus current, power consumption and segment design.
Installation Requirements
Use only in combination with an HS810, HS820 or HS840 head station. Confirm that the system supply is 20 V to 35 V DC before installation. Distinguish the power terminals, DP terminals and PA terminals when wiring. PROFIBUS PA segment cabling must conform to the PROFIBUS PA wiring specification. Do not connect intrinsically safe field devices directly to the non-intrinsically safe PA segment. For installation in Zone 2, observe the electrical rules for explosion-protected areas. Keep the module away from heat sources and ensure adequate ventilation. Check terminating resistors and polarity after wiring is complete.