ABB LT2005-S/SP19 3BHB014827R0001

Product Name​
LT2005-S/SP19 Current Transducer
Product Introduction​
Closed-loop Hall-effect current transducer designed for high-power drive systems. Primarily used in ABB ACS6000 medium- and high-voltage frequency converters for main circuit current measurement and overcurrent protection.

Detailed content

Technical Specifications​
  • Technology: Closed-loop Hall effect
  • Primary Rated Current: 2000 A RMS
  • Measuring Range: 0 to ±3000 A
  • Secondary Rated Current: 400 mA RMS
  • Transformation Ratio: 1:5000
  • Supply Voltage: ±15 V to ±24 V DC, ±5% tolerance
  • Accuracy: ±0.3% at 25 °C
  • Linearity Error: <0.1%
  • di/dt Capability: 100 A/µs
  • Bandwidth: 100 kHz
  • Response Time: <1 µs
  • Overload Capacity: 3 times rated current
  • Insulation: Primary/secondary electrical isolation
  • Operating Temperature: -10 to +70 °C
  • Storage Temperature: -25 to +85 °C
Functional Features​
  • High-precision DC, AC, and pulse current measurement
  • Full electrical isolation between power and control circuits
  • Fast dynamic response
  • Strong overload resistance
  • Low temperature drift
  • Compatible with high-power inverter control systems
Application Scenarios​
  • ACS6000 medium-voltage drives
  • Rolling mill main drives
  • Large fan and pump systems
  • Rectifiers and inverters
  • Industrial power test platforms
Material Composition​
  • Flame-retardant plastic housing, UL 94-V0 grade
  • Epoxy-sealed magnetic core
  • Precision Hall sensor
  • Copper primary conductor path
  • Industrial connector terminals
Structural Characteristics​
  • Panel or busbar mounting style
  • Through-hole primary conductor design
  • Shielded signal output
  • Heavy-duty industrial enclosure
  • Approximate weight 1.86 kg
Working Principle​
The transducer uses Hall-effect closed-loop compensation. The magnetic field generated by the primary current is measured and compensated by a secondary current that accurately represents the primary current.
Installation Requirements​
  • Install with correct primary current direction
  • Use torqued busbar connections
  • Keep signal cables separated from power cables
  • Provide stable bipolar auxiliary power
  • Ensure adequate ventilation and cooling
Usage Precautions​
  • Never exceed insulation and overload ratings
  • Avoid mechanical stress on terminals
  • Calibrate zero offset before commissioning
  • Verify SP19 customization compatibility with target drive

You may also like