Detailed content
Ordering Data
- Standard Version: CM572-DP, order number 1SAP170200R0001
- XC Version: CM572-DP-XC, extended-condition version
Technical Specifications
- Protocol: PROFIBUS DP, DPV0 and DPV1
- Interface: 9-pin D-Sub female socket
- Transmission Standard: RS-485 according to IEC 61158 / IEC 61784
- Transmission Rate: 9.6 kbps to 12 Mbps
- Network Role: PROFIBUS-DP master
- Power Supply: From AC500 CPU terminal base
- Isolation: Potential-separated bus interface
Functional Features
- Cyclic process data exchange
- Acyclic diagnostic and parameter access
- Multi-master functionality
- Remote I/O, drive and valve-terminal integration
- LED indicators for power, ready, run, station status and error
Structural Characteristics
- Compact AC500 communication expansion module
- Pluggable D-Sub PROFIBUS connector
- Installs on AC500 terminal base
- Designed for control-cabinet mounting
Environmental Parameters
- Operating Temperature: 0°C to +60°C typical
- Storage Temperature: -40°C to +70°C
- Humidity: 5% to 95% RH, non-condensing
- Protection Rating: IP20
Application Scenarios
- Packaging and assembly lines
- Water treatment and process skids
- Machine centers and OEM machinery
- Distributed I/O networks
- Legacy PROFIBUS device integration
Installation Requirements
- Mount on compatible AC500 terminal base
- Configure module in Automation Builder
- Use correct PROFIBUS device description files
- Install bus termination at physical network ends
Usage Notes
- Actual node count depends on repeater configuration
- All devices must use identical baud rate and PROFIBUS parameters
- Avoid mixing CM572 power-module descriptions with CM572-DP communication module identity












.jpg)