Digital guide

You are here:

ABB AI 723F

Product Name
ABB AI 723F analog input module
Product Introduction
The ABB AI 723F is a 16-channel analog input module in the S700 I/O family. It acquires analog field signals and resistance temperature detector measurements, converts them into digital values, and transmits the data to a Freelance controller or PROFIBUS remote I/O station.

Detailed content

Technical Specifications
  • Number of channels: 16
  • Channel arrangement: two groups of eight
  • Supported signals: 0–10 V, -10 to +10 V, 0–20 mA, 4–20 mA
  • Temperature inputs: Pt100, Pt1000, Ni1000
  • RTD wiring: 2-wire or 3-wire
  • Optional use as digital inputs
  • Resolution: 12 bits plus sign
  • Voltage input impedance: greater than 100 kΩ
  • Module power supply: 24 V DC
  • Dimensions: 67.5 × 76 × 54 mm
  • Weight: approximately 0.15 kg
Function Features
  • Individually configurable input channels
  • Voltage, current, RTD, and digital-input capability
  • Electrical isolation between field inputs and module electronics
  • No potential separation between channels
  • PROFIBUS remote I/O operation
  • Direct I/O for AC 700F and AC 900F controllers
  • Compatible terminal units: TU 715F and TU 716F
Application Scenarios
  • Pressure, temperature, flow, and level monitoring
  • Chemical and petrochemical process control
  • Power generation and water treatment
  • Industrial furnaces and building automation
  • Freelance DCS signal acquisition
  • Remote I/O stations in large process plants
Performance Parameters
  • Measurement resolution: 12 bits plus sign
  • Typical measurement accuracy: approximately ±0.1% of full scale at 25 °C
  • Suitable for continuous industrial process measurement
  • Real-time transmission of converted measurement values to the controller
Material Composition
  • Industrial-grade module housing
  • Printed circuit board with analog signal-conditioning and conversion circuits
  • Spring-clamp field terminals
  • Backplane connector
  • Electrical isolation components
Structural Features
  • Standard S700 modular design
  • Rear backplane bus connector
  • Front-facing field wiring terminals
  • Mounts on a DIN-rail terminal unit
  • Slim, high-density industrial I/O form factor
Working Principle
Each channel receives a voltage, current, or RTD resistance signal. Current inputs use a precision shunt, while RTD inputs use a measured excitation current and known reference resistance. The module conditions the signal, performs analog-to-digital conversion, and sends the digital measurement to the controller through the backplane or PROFIBUS interface.
Installation Requirements
  • Mount the terminal unit on a standard 35 mm DIN rail
  • Install inside a suitable control cabinet
  • Use the correct terminal unit for the selected wiring configuration
  • Follow two-wire or three-wire RTD connection rules
  • Separate analog and power cables
  • Use ESD protection when handling the module
Usage Precautions
  • Channels are not isolated from one another.
  • Do not exceed the configured voltage or current range.
  • Configure each channel in the control system before commissioning.
  • Do not hot-swap the module.
  • Verify sensor type, wiring, and calibration during commissioning.

You may also like